Asphalt Odor Control
GMI was hired by a large energy and holding facility to capture the escaped odor from their bulk asphalt tanks at a coastal facility. When doing tank transfers and product moving, the tanks odor was captured by the coastal winds and created issues for neighboring residents. GMI worked closely with our customer to find the best solution for both Odor Control, System Function, and Serviceability.
The tested Asphalt in the system came back with a very acidic PH reading which lead GMI to use Stainless Steel piping to capture the exhaust. This specific tank supported four exhaust ports from the roof, which were all captured to a drip leg and bucket tee designed for optimal air flow and draining. All piping was supported to ASME code at a height of 14’ which would allow the terminal access under the pipe safely with equipment. Concrete supports were drilled and poured below frost line to capture the loaded stress of the 12” stainless pipe. All piping was properly pitched to allow for the capture of condensate return of the odor back into IBC holding tanks.
To house the new Stainless Steel odor system, GMI retrofit an existing pad and back wall to house the Odor Control Equipment. As the Asphalt showed highly acidic properties, a standard Carbon Steel Carbon bed would not prove adequate for the application and GMI fabricated and installed a new 316ss Carbon Bed for this application with a custom screen system to hold the Carbon Media.